The Artisans of Igun — Brass Casters and the Secrets They Pass Down A deep cultural story of Benin’s legendary bronze casters, their skills, beliefs, and survival in a modern world. 📚 Table of Contents Introduction — A street where history breathes Origins of Igun Street & the Benin Kingdom The lost-wax casting method explained simply Apprenticeship, secrets & sacred knowledge Spiritual beliefs behind the bronze Colonial encounter & the Benin Bronzes Modern Igun: survival, tourism & adaptation Watch: Igun Street & Benin Bronze videos Lessons for today’s youth & artisans Further reading & Google search links 🧭 Introduction — A street where history breathes In the heart of Benin City, Edo State, Nigeria, lies a street unlike any other — Igun Street . To the casual visitor, i...

Alternator Care & AVR Calibration — Step-by-Step Tests

Alternator Care & AVR Calibration — Step-by-Step Tests

By --

This practical guide explains alternator care and AVR (Automatic Voltage Regulator) calibration with safe, step-by-step tests you can run on-site. Ideal for technicians, repair shops and maintenance engineers — includes inspection checklists, static and dynamic tests, common faults, and repair advice. Keywords: AVR adjustment, alternator voltage problem.

Why alternator care and AVR calibration matter

The alternator (generator head) and its AVR determine the quality and reliability of the electrical output. Poor alternator maintenance or mis-adjusted AVR leads to unacceptable voltage regulation, equipment trips, harmonics, overheating and premature failure. Proper care and correct calibration save downtime and costly repairs.

Quick safety reminders — read before you begin

  • De-energise appropriately: Isolate the alternator and switchgear as required. Many tests require the alternator to be both de-energised and then run live — follow lockout/tagout (LOTO) procedures.
  • PPE: Insulated gloves, eye protection and hearing protection while running tests under load.
  • Engine/exhaust safety: Use exhaust extraction or run outside. Ensure adequate ventilation to avoid CO poisoning.
  • Use the right tools: True-RMS meters, clamp meter, insulation tester (Megger), oscilloscope (optional), diode tester, variac (if needed), and the manufacturer’s AVR manual.

Overview: alternator components & AVR roles (short)

Alternator main parts: stator windings (output), rotor (field), exciter/brushes or brushless exciter system, slip rings (if brush-type), diodes/rectifier, bearings, AVR.
AVR responsibilities: supplies field current to rotor; senses output voltage; adjusts excitation to maintain setpoint; provides stability (gain/droop) and protective behaviour.

Tools & test equipment checklist

  • True-RMS multimeter (DC and AC)
  • Clamp meter (with inrush capability)
  • Insulation resistance tester (Megger)
  • DC millivoltmeter (for field current)
  • Diode tester / bridge tester
  • Oscilloscope (for waveform/AVR dynamics)
  • Battery charger/tester and jump leads
  • Screwdrivers, torque wrench, feeler gauges, brushes (spare)

Routine visual & mechanical checks (preliminary)

  1. Inspect alternator exterior for oil leaks, coolant contamination, loose fasteners and belt condition.
  2. Check bearings for abnormal play or noise; look for grease leaks.
  3. Inspect brush holders & brushes: check spring tension, brush length, and seating. Replace brushes that are below minimum length.
  4. Check slip rings: surface should be smooth and free of pitting or heavy grooves. Light polish if required (use fine emery or stone) and remove residue.
  5. Inspect stator windings for signs of overheating (discoloration) and ensure stator ventilation passage is clear.
  6. Check all terminations and protective covers; tighten terminal lugs to recommended torque.

Electrical tests (de-energised)

Perform these with the alternator isolated and LOTO applied.

1. Insulation resistance test (megger)

  1. Disconnect alternator leads from switchgear and isolate rotating field circuits.
  2. Test stator to earth: apply 500–1000 V DC (per manufacturer) and record insulation resistance (IR). Good machines ≫ 1 MΩ; many specify 1–5 MΩ minimum depending on rating and humidity.
  3. Test rotor field circuit to earth and rotor windings similarly.
  4. Record values and compare to previous readings — a declining trend suggests moisture/contamination.

2. Winding continuity & resistance

  1. Measure phase-to-phase resistance (stator) and compare to nameplate or manual values. Small differences expected; large deviations indicate winding damage or shorted turns.
  2. Measure DC resistance of field winding — low or open circuits indicate faults.

3. Diode / rectifier test (for brushless or rectifier-equipped machines)

  1. If rectifier bridge used, test diodes with diode test mode: forward drop ~0.5–1.0 V; reverse should be open. Replace faulty diodes.

Pre-run checks (before live tests)

  • Re-connect wiring per manual. Ensure all removable covers are installed.
  • Confirm battery bank health and alternator starting battery charged — AVR excitation depends on reliable DC supply.
  • Record ambient temperature and expected no-load conditions.

Initial live tests — no-load excitation & AVR bench checks

Start the alternator/engine and perform these tests carefully while observing the control panel and instrument readings.

1. Excitation & field current check

  1. With AVR in automatic mode and generator running at rated speed (or idle if specified), measure DC field current at the AVR field current terminal using a DC ammeter. Record the value.
  2. If field current is zero but AVR sensing voltage present, check exciter/diode bridge (brushless) or brushes/slip rings (brush-type).
  3. Compare measured field current with expected values from manual for no-load condition (typical ranges vary by size; document readings).

2. No-load voltage check

  1. Allow the alternator to reach rated speed. Measure phase-to-phase (line) voltages and phase-to-neutral voltages (if neutral available).
  2. Typical tell: V_LL should be near nameplate (e.g., 400 V nominal). If excessively low or high, AVR adjustment or fault is suspected.

AVR basics before adjusting

Most modern AVRs have these controls/parameters (labels vary): Voltage set (V-set), Voltage gain (V-gain), Stable (stability), Droop, and sometimes Current limit or Power factor compensation. Always consult the AVR manual for control locations and recommended ranges.

Step-by-step AVR calibration (typical procedure)

Note: These instructions are general. Follow your AVR/alternator manual for exact procedures and safety limits.

  1. Set AVR to manual control (if present) then to automatic: Some AVRs allow local manual field adjustment — start in auto to verify behaviour, then switch to manual for controlled adjustments if needed.
  2. Set voltage setpoint: Using the AVR V-set potentiometer, adjust until the unloaded generator measures nominal voltage (e.g., 400 V LL). Turn slowly and allow settling between small adjustments.
  3. Check phase voltages and balance: Verify that all three phase voltages are within ±1–2% and balanced. If one phase differs significantly, investigate wiring or static excitation issues.
  4. Adjust AVR gain (stability): Increase gain slightly if voltage droops under rapidly applied load, but too much gain causes oscillation. Typical approach: set gain low, apply small step load, if voltage droops and recovers slowly increase gain until response is prompt without oscillating. If oscillation occurs reduce gain.
  5. Test voltage regulation under step load: Apply a moderate resistive load (e.g., 25% rated) quickly and observe voltage dip and recovery. Good regulation: small dip (<5% depending on generator) and recovery in a few seconds without overshoot.
  6. Reactive load & power factor test: Apply lagging reactive load (motor or inductive bank) and check AVR maintains voltage within limits and does not over-excite (overvoltage) or under-excite.
  7. Set droop (if paralleling): If generator will operate in parallel with other units, set droop per paralleling requirements (e.g., 3–5% droop). This prevents hunting and regulates load sharing. For standalone operation, droop is typically zero/isochronous.
  8. Verify stability across speeds: If possible test small speed variations and confirm AVR does not produce voltage hunting or instability.
  9. Lock down settings & record values: Label the AVR panel with final dial positions and record field current and voltage setpoint values in the service log.

Detailed test examples (digit-by-digit style)

Example: Adjust V-set to 400 V (line-to-line)

  1. Measure current V_LL (say measured 392.0 V).
  2. Turn V-set slowly clockwise by a small amount (manufacturer often recommends small turns ~1/8). Wait 10–15 s for settlement.
  3. Re-measure; suppose new reading 396.8 V. Turn again until reading ≈ 400.0 V.
  4. Record the number of clicks or pot position for future reference.

Example: AVR gain tuning (stability)

  1. Start with gain low (min). Apply a step load (e.g., switch resistive bank to 25% rating).
  2. If voltage falls 8% and recovers slowly, increase gain slightly. If oscillation or overshoot occurs, reduce gain a small amount.
  3. Goal: voltage dip under step <5% and recovery to setpoint in <5 s without ringing.

Dynamic (loaded) tests and acceptance

  1. Perform staged load test: 25% → 50% → 75% → 100% (allow 5–10 minutes at each stage), monitor voltages, frequency, temperatures, field current and AVR behaviour.
  2. Watch for tripping events, abnormal heating, abnormal brush arcing, or voltage instability.
  3. Record values and compare to manufacturer acceptance criteria.

Troubleshooting common alternator/AVR problems

  • High output voltage (overvoltage): AVR V-set or gain too high; faulty voltage sensing; AVR internal fault. Action: reduce setpoint/gain; verify sensing leads; test AVR on bench or replace.
  • Low output voltage / cannot build voltage: Excitation failure (AVR fault, field open, diode bridge failure, battery supply), loose brushes, or bad connections. Action: check field circuit continuity, diodes, battery/excitation supply and brushes.
  • Voltage hunting / oscillation: AVR gain too high, poor AVR tuning, bad sensing wiring, poor governor/engine speed control coupling. Action: reduce gain, check wiring and governor stability.
  • Phase voltage imbalance: winding damage, stator shorted turns, or unequal excitation. Action: measure winding resistances, test insulation, and inspect for physical damage.
  • Sparking at brushes: poor brush seating, worn commutator/slip rings, incorrect brush spring tension. Action: replace/seat brushes and clean slip rings.

When to repair vs replace

  • Replace AVR if internal components fail or bench test shows incorrect behaviour. AVRs are often modular and replaceable.
  • Repair alternator winding faults at specialist rewind shop if shorted turns or stator damage found.
  • Brush-type maintenance: brushes and slip rings can be serviced on site; major rotor failures require workshop work.

Maintenance schedule (recommended)

  • Daily/weekly: Visual check, brushes, battery voltage.
  • Monthly: Run under load, record voltages, check AVR response.
  • Quarterly: Check insulation resistance, brush lengths, slip ring surface.
  • Annually: Comprehensive test: insulation test, full load bank test, diode test and AVR recalibration.

Tools, spare parts & consumables to carry

  • Spare brushes & springs
  • Replacement AVR (common model stock)
  • Replacement diodes / rectifier modules
  • Cleaning supplies (lint-free cloth, isopropyl alcohol), emery cloth for slip rings
  • Torque wrench, insulation tester, clamp meter, DC ammeter

Embedded training videos (classroom & workshop friendly)

Watch these practical video walkthroughs to see the steps in action. Replace with your own videos if preferred.

Quick diagnostic checklist (one-page)

Alternator & AVR Quick-Check
1. Visual inspection: oil, cooling, belts, mounting, vents.
2. Brush & slip ring check: length, spring tension, surface.
3. Insulation resistance: stator & rotor to earth (Megger).
4. Diode test: forward/reverse checks.
5. Start and measure: V_ll, V_ph, I_field, phase balance.
6. Adjust AVR V-set to nominal; tune gain for stability.
7. Step load: 25/50/75/100% - monitor recovery & temps.
8. Record and label final AVR settings.
    

Google quick-search links & manufacturer references

Internal links

FAQ

Q: My alternator voltage drifts under small load — is it AVR or excitation?
Often it’s AVR gain or sensing wiring. Start by checking sensing leads, then tune AVR gain; also check engine speed stability (governor).
Q: Can I bench test an AVR?
Yes — many AVRs have bench test procedures (apply DC excitation and simulated sensing). Follow the manufacturer’s bench test guide and safety steps.
Q: How often should I replace brushes?
Inspect brushes quarterly and replace before they fall below the manufacturer's minimum length. Replace if springs weaken or if heavy arcing observed.